10kVA Vectronic Online UPS (C Series with batteries)


Profile:               Tower
Rating:               10kVA
Voltage:             220/230Vac
Frequency:        50Hz

1,400,000.00 1,500,000.00

Product specifications:

Input                                                                                                     
Voltage230 Vac
Tolerance Normal Over-voltage:       +10%
Withstand Over-voltage:   +15% (20% max limit)
 Normal Under-voltage:      – 20%
Withstand Low-voltage:      – 30% (-37% lowest limit)
Power Factor0.98
Output   
Voltage     230Vac ± 1%
Power Factor0.8
 0.9
Transfer Time    0 ms
Frequency46 – 54Hz (On Mains)
 50Hz (On Battery)
Waveform                     Pure Sine WaveSet product image
THDiLinear Load ≤ 3%;     Non-linear Load ≤ 6%
Crest Factor 3 : 1
Bypass FacilityFS Model:       Static Bypass
 FS-V Model:   Both Maintenance Bypass and Static Bypass
DC Bus / DC Functions:                     
1kVA36V
2kVA72/96V
3kVA96V
6/10kVA192V / 240V
Cold-Start FunctionYes
Charging Time  6hr to recover to 90% capacity
Battery Charging in OFF Mode   Yes
Battery TypeSealed, Maintenance-free VRLA
LCD User Interface:            
Metering / Indications forVoltage
 Load %
Frequency
 General Status
Alarm
Communication:            
Interfaces RS232, USB*, SNMP*                          (* Option)
Overload 
100~110%Output swithes to bypass after 60s
125~130%Output swithes to bypass after 30s
 >130%Output swithes to bypass after 100ms
Environment:       
Temperature      0 ~ 40oC
Humidity      20 ~ 90% Non-condensing
Noise Level             < 50dB from 1m
IP Class20
Physical: 
Dimensions  (mm)        1kVA      :       145 x 405 x 220 (W x D x H)
 2-3kVA   :       192 x 460 x 340 (W x D x H)
6-10kVA :       248 x 500 x 460 (W x D x H)
Weight (Kg)1kVA      :       14kg
 2kVA      :       34kg
 3kVA      :       34.5kg
 6kVA      :       57kg / 192V:          90kg / 240V
 10kVA    :       60kg / 192V;          93kg / 240V